Nvidia's 45°C inlet spec is quietly killing the datacenter chiller

45°C inlets just killed the chiller. Most people haven't noticed yet

At SC26 in Chicago, cooling dominated the show floor, and the number everyone was talking about was Nvidia's 45°C liquid inlet temperature. That jump from the usual 30–35°C lets rooftop dry coolers do the work once handled by chillers, cutting cooling energy 50–70 percent, total datacenter power 10–20 percent, and water use by 80–95 percent. The catch: retrofits still need real engineering work on loops, flow rates, and pressure drops.

What's missing here? It's the chillers. You won't need them anymore.
  1. viktorcode

    > We're approaching a point where industry advances are answering many of the objections (the real ones, not the hysterical ones) raised by the anti-data center movement.

    AFAIK the main objections are against sharing the electricity bill and tax exemptions in exchange for a paltry amount of jobs created. Does the author classify those as hysterical?

    Also, the existence of technologies does not mean the data center next door will use them. For instance, many can run on closed water loops, but prefer not to, because it is cheaper.

  2. helsinkiandrew

    Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178

    I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan

  3. iamniels

    This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.

    I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.

  4. GMoromisato

    This also makes orbital datacenters more economical since radiators can be smaller at higher temperatures.

  5. __MatrixMan__

    That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.

  6. throw0101c

    ASHRAE TC 9.9, "Mission Critical Facilities", members are IT folks, and they have defined a Category/Class "A4" that have dry-bulb operating temperatures in the 5-45˚C range:

    * https://www.upsite.com/blog/the-importance-of-mutual-underst...

    There's also:

    > For those familiar with the liquid cooling guidelines, the most obvious change will be that of the Liquid Cooling class designations. Previously, the classes were designated W1, W2, W3, W4 and W5. Each of those classes had a lower temperature limit of 2°C, while the upper limits were 17°C, 27°C, 32°C, 45°C, and Over 45°C respectively. The deficiency in the original designations didn’t really appear until the debate began over adding a class between 32°C and 45°C.

    > […] In the end, due to the need for enhanced flexibility, not to mention making it easier for users to remember what temperature goes with the Class, the 5th Edition redesignated the classes based on their upper temperature limit – therefore the classes are now W17, W27, W32, NEW class W40, W45, and the now named W+.

    * https://www.upsite.com/blog/what-you-need-to-know-about-ashr...

    So >35C isn't entirely unknown already.

    * https://www.ashrae.org/technical-resources/bookstore/datacom...

    * https://greencalculus.com/standards/ashrae-tc-9-9-thermal-gu...

  7. leni536

    I assume this also means more water moved for the same power and target die temperature. I wonder what other engineering considerations follow from that.

  8. Waterluvian

    Are there any Factorio-like games that treat heat gradients as a kind of spatial resource? Like in some sci fi factory you’ve got an iron smelter pressed right up against your data refinery?